Wire Size Calculator

Enter the load, the distance and the voltage. This returns the smallest conductor that satisfies both the ampacity requirement and the voltage-drop target — which are different limits, and on a long run the drop is the one that decides.

Your numbers

Result

Wire size (AWG)
10
AWG
Size for ampacity alone
12AWG
Size for voltage drop alone
10AWG
Actual drop at this size
2.07%
Volts dropped
4.97V
Ampacity of chosen wire
30A
Circular mils
10,380cmil
Circular mils needed for drop
7,167cmil

How this is calculated

  • Circular mils needed = (phase factor × K × amps × one-way length) ÷ (allowed drop % × volts).
  • The chosen size is the first AWG that satisfies BOTH the ampacity table and the circular-mil requirement.
  • Ampacity figures here are the 75°C copper column of NEC Table 310.16, and aluminium carries less for the same size.

Before you order

  • Two different limits are at work. On a short run ampacity decides; past about 100 feet voltage drop usually decides, and it is the one people forget.
  • Ampacity has to be derated for ambient temperature, for more than three current-carrying conductors in a raceway, and for the terminal rating of the equipment — often the 60°C column, not 75°C.
  • Aluminium needs roughly two sizes larger than copper for the same job, plus antioxidant compound and terminals listed for it.
  • This is a planning tool. The NEC and your inspector are the authority.